November 1, 2018

METRO LIGHT RAIL

Gets On-Board with Storm Water Harvesting Solution

Santa Monica, CA

DESIGN & CONSTRUCTION TEAM

Lead Designer: Maintenance Design Group, Pasadena, CA
Civil Designer: W2 Design, Inc., Pasadena, CA
General Contractors: Kiewit Building Group, Inc., Santa Monica, CA
Installing Contractor: Murray Company, Newbury Park, CA
System Manufacturer: Oldcastle Infrastructure, Fontana, CA

California’s struggle with drought has emphasized the need for sustainable water use; an issue that transcends its borders. The U.S. Drought Monitor reports that at some point over the past decade, nearly half of the U.S. has been in some form of severe drought.

Rainwater or storm water harvesting is one approach to meet the challenge. Case in point is the construction of the Expo Rail Operations & Maintenance Facility in Santa Monica, California for the Metropolitan Transportation Authority (METRO). While it meets operational demands for the region’s increased transportation needs, it also creates impermeable surfaces that require innovative storm water management approaches.

Located on 8.3 acres, the new Operations & Maintenance Facility complex includes a 75,000-square foot main building, a 9,500-square foot secondary structure, a 6,000-square foot maintenance building with an automated vehicle washer that includes a reverse osmosis rinsing machine with a 100% water reclamation system, a 4,500-square foot servicing platform, a paved roadway and two adjacent parking lots.

THE CHALLENGE

Landscape irrigation, vehicle washing and other water needs required an estimated 5,500 gallons per day at the new facility. Focusing on “green” building and energy efficiency, METRO officials sought a Low Impact Development (LID) design with zero storm water runoff. Poor soil conditions precluded soil infiltration to replenish aquifers. As a result, the best option was a storm water harvesting system for non-potable uses to reduce reliance on city water.

THE SOLUTION

Oldcastle Infrastructure assembled a team to provide the total storm water management system including a 400,000 gallon StormCapture cistern, an upstream pretreatment unit, and a downstream storm water harvesting system from Water Harvesting Solutions (WAHASO). The Murray Company installed the pretreatment and StormCapture systems during the spring of 2014. The harvesting equipment was later installed in August 2014. The facility finally became operational in May 2015.

The solution leverages across-the-board efficiencies in water use by reducing the impact on the municipal water supply, land footprint, system maintenance time and budgetary concerns. “Oldcastle has a diverse portfolio of products that afforded the project economies of scale and met the required 50-year design life,” notes Patrick Wong, W2 Design president and senior project manager.

The 400,000-gallon StormCapture system – occupying a small footprint under the parking lot due to large storage capacity per square foot of area – utilizes 29 StormCapture precast concrete modules measuring 12-feet high x 7-feet wide x 15-feet long. One unique aspect of the project: one module in the layout is deeper than the others and houses an integrated pump station to supply water for the harvesting system.

“Our standard modules for the project are 12-feet deep. We supplied one 7-foot x 15-foot module which is 13-feet deep. It is used to completely drain down the system and allow full utilization of the entire 400,000 gallons of storage capacity,” notes Jason Herrman, engineering manager for Oldcastle Infrastructure.

Other components included nine precast concrete link slabs measuring 9-feet wide x 17-feet long that were used at interior locations instead of full modules, and five standard rings up-to-grade with cast-iron lids (manholes) located at ground level for maintenance access. The system also has a 40- mil HDPE liner, with geotextile fabric.

Storm water runs from the rooftop downspout leaders and impermeable ground surfaces into the onsite storm drain system. The baffle box screening and hydrodynamic separation is designed to effectively remove sediments, Total Suspended Solids (TSS) and hydrocarbons. Trash and debris, organics and gross solids collect in a raised screening basket, where pollutants dry out between storm events.

Pretreated storm water flows into the StormCapture system’s concrete cistern modules, temporarily storing it for harvesting purposes. Water from the cistern exits into the concrete pump station module which also serves as an internal storm system overflow bypass should the cistern be filled to capacity during an extreme rain event.

In response to increased non-potable water demand, a drop in the system pressure signals the pump station’s main pressurization submersible pumps – duplex variable frequency drive pumps providing 70 GPM at 67 PSI – to begin operating to meet the demand. The pumps cycle back and forth to equalize wear. Should one pump fail, the second pump can meet demand.

The pumps direct storm water up through the WAHASO harvesting equipment package located in an above-ground enclosure. In the first step, a mechanical filter removes particulates down to 50 microns. In the second phase, a bag filter removes remaining particulates down to 5 microns. Water is then sanitized with ultraviolet light rated to handle 70 GPM to kill harmful bacteria or pathogens, ensuring safe water for public exposure during irrigation and vehicle washing.

“We are able to capture all of their runoff in this one underground system, allowing them to keep their parking lot intact and provide the space they need, as well as the desired sustainable benefits of harvesting water. In addition, the 400,000 gallon cistern was leak tested to confirm water tightness after installation,” Hermann points out. “It passed the test.“

The harvested water will be used for irrigation of facility landscaping and for train washing. The extensive train wash system features both manual and automated wash stations with reverse osmosis and water reclamation, and has a capacity of six rail cars at once. “Out of 10 gallons of water, only two are ‘wasted’ through evaporation or splashing onsite. The water harvesting system is designed to capture close to 50% of the annual rainfall typical to the area, which historically is dry in mid-summer,” notes Wong.

“California gets seasonal rains but the cistern is large enough for us to harvest retained water over a period of months to maximize the system’s value,” says John Bauer, WAHASO president. A municipal water bypass valve automatically opens when water in the pump station and StormCapture cistern drops below a pre-set level. WAHASO’s WCS100 control system logs and reports the amount of water available in the cistern, how much is captured for harvesting purposes, and the amount of municipal water demanded by the system.

WAHASO also integrates OptiRTC technology from GeoSyntec into its storm water harvesting systems, which uses predictive modeling to actively determine storm water detention requirements and release only as much stored water as necessary to meet capacity requirements for each forthcoming storm event. OptiRTC monitors local weather forecasts and onsite device inputs to anticipate storm flows to detention within 24 hours of occurrence. It lowers cistern storage levels ahead of the precipitation event in proportion to the expected storm volume, and closes the outlet valve during storm events to capture and retain water for harvesting.

“Without the OptiRTC capability of actively managing the cistern level, we would have been required to meter out all detained water over a short period of time, minimizing any real value of the harvesting system,” explained Bauer. All systems designed by WAHASO achieve NSF/ANSI 350 standards for water reuse treatment systems, which defines acceptable water quality for surface irrigation, toilet flushing, cooling tower make-up and other nonpotable uses.

GOING FORWARD

The system was designed to minimize maintenance by onsite personnel. Sediment and other debris captured by the pre-filter must be periodically evacuated to keep the cistern free of sediment and organic matter, especially first-flush debris after major rain events. In the filtration skid, bag filters are typically changed every four to eight weeks and the UV bulbs are replaced ,every 10,000 hours, which equates to a year of continuous use.

“The storm water management techniques are set to contribute from one to four points toward a LEED gold rating,” says Renee Azerbegi, president and project manager for Ambient Energy, a consultant engaged by Maintenance Design Group for LEED project facilitation.

“Because of the drought, water conservation issues are being significantly heightened,” notes Wong. “Technology for pre-treatment, post-treatment and storage is available today. Storm water treatment and management is certainly here to stay.”

oldcastleinfrastructure.com

Download Full Case Study